DAE CT-600SB Split-Core Current Transformer 600A (600:0.067A) — 1.38" Inside Dia.
Split-core Current Transformer, model DAE CT-600SB, rated 600A (600:0.067A) with a 1.38" inside diameter. Outside dimensions: 2.36" x 3.54" x 1.57". Unit weight: 15 oz. Supplied with a 38 inch, 20AWG lead wire. Electrical accuracy is 1% with a frequency range of 50–60Hz and internal windings: 9,000. This CT is compatible with all the DAE electric meters. Installation guidance: 1 CT for each 120v 1 phase 2 wire (1 hot wire, 1 neutral) circuits or electrical panel; 1 CT for each 240v 1 phase 2 wire (2 hot wires) circuits or electrical panel; 2 CTs for each 120/240V 1 phase 3 wire (2 hot wire, 1 neutral) electrical panel; 2 CTs for each 208V or 480V 3 phase 3 wire (3 hot wire, no neutral) electrical panel; 3 CTs for each 120/208V or 277/480V or 347/600V 3 phase 4 wire (3 hot wire, 1 neutral) electrical panel. Ensure the arrow on the CT is aligned with the circuit orientation. Do not disconnect the 2 wires from the CT while the circuit is energized. If the circuit is live and the CT is not connected to a meter, join the 2 wires from the CT to prevent damage. Factory Calibration Certificates are available. DAE Controls LLC is a Minority Business; the NMSDC Minority Supplier Certificate can be obtained from the DAE Controls website. For buyers outside of USA, carriers may charge a brokerage fee in addition to tax.